A
Study of the Energy Savings that can Occur when Using
INSULADD® Solar Reflective Paint on Irradiated Building Walls
For Tech Traders
By
H. F. Poppendiek, April 2003
GEOSCIENCE LTD
6260 Marindustry Drive, San Diego,
California 92121

Photograph of the solar lamp array
and INSULADD® painted wall panel.

Photograph of the millivolt
recorder and solar lamp array
INTRODUCTION
Geoscience was requested by Mr.
David Page to perform several tasks relative to the energy savings that result when using INSULADD paint on the outside of the building envelope. One task
dealt with comparative outer wall panel surface temperature and corresponding heat flux
measurements for the solar irradiated panels painted with Insuladd paint as well as with
ordinary paint. A second task involved determining the additional panel thermal
resistances that would have to be added to insulated wall systems painted with ordinary
paint to yield the low thermal heat fluxes through a building wall when using Insuladd
paint on the outer surface. The last task that was requested involved defining a
mathematical thermal wall model so that the equations can be used to calculate wall
thermal performance characteristics when system parameter changes occur.
MATHEMATICAL
THERMAL WALL OR ROOF MODEL
An elementary model has been
used which gives the steady state wall or roof temperature and the required heat removal
to maintain a given room temperature when the outside weather conditions are known. The
heat balance for this system is,

The equation used
to determine the air conditioning load is,

THE EXPERIMENTAL SYSTEM
A wall panel having an R-value
somewhat typical of a building wall, namely, R = 12 hr ft2
°F/Btu, was
instrumented with surface thermo-couples, as well as a large, thin calibrated heat flux
transducer. The vertical test panel front surface faced a battery of sun lamps that
provided the simulated solar irradiation. The heat flux transducer was located in the
middle of the vertical panel. Heat absorbed on the front surface of the panel was lost 1)
by conduction through the panel into the air behind it and 2) by infrared radiation and
natural air convection from the front surface of the panel.
THE TEST PROCEDURE
From the hot and cold panel
surface temperatures, the front and back ambient air temperatures and the heat flow
transducer heat flux measurements; the system R-values were determined. One set of
measurements was made for the Insuladd-applied paint and the other set for ordinary house
paint. From the two sets of data, one can obtain the energy savings and the additional
thermal resistance that would have to be added to the panel with ordinary paint to get the
reduced heat flux attained by the panel with INSULADD® added
paint.
TEST
RESULTS
The test results for the
insulation panel with its outer surface painted with INSULADD®
paint follow:

The test results for the
insulation panel with its outer surface painted with ordinary (light green) latex house
paint follow:

On the basis of these two sets
of data, the energy savings obtained when using the INSULADD®
paint instead of an ordinary paint is,

It is also pointed out
that if one added an additional thermal resistance of Radd. = 6.0 hr ft2
°F/Btu to the wall
system having the ordinary house paint on its outer surface, the higher heat flux being
conducted into the building, namely, 5.24 Btu/hr ft2
would be reduced to
the lower heat flux value of 3.57 Btu/hr ft2
for the wall painted
with INSULADD® paint. This additional resistance calculation
is performed by a trial and error calculation using Equation (1) (by iterating Rr, t and q/A).
CONCLUDING
COMMENTS
It is pointed out that the
energy savings terms and add, values are not just functions of the solar reflectivities
and IR emissivities, but also of the Rr
and system
temperature information. It is also to be noted that ordinary paints can have a range of
solar reflectivities and IR emissivities, depending upon their chemical constituency.

A STUDY OF THE
ENERGY SAVINGS THAT CAN OCCUR WHEN USING INSULADD® SOLAR
REFLECTIVE PAINT ON THE INSIDE OF BUILDING WALLS.
For
Tech Traders
By
H.
F. Poppendiek, April 2003
GEOSCIENCE LTD
6260 Marindustry Drive, San Diego,
California 92121
Introduction
If
the emissivities in the infrared region of interior wall paints are lower than ordinary
paints, then the radiant heat transfer from the outer walls of rooms can influence the
energy savings and comfort of persons in the rooms. Under wintertime conditions, where
furnace heating is normally required in residences and buildings, if the interior wall
paints have lower emissivities than normal paints, ambient room temperature cooling would
be less and the comfort level of persons in the rooms would be greater.
Specifically,
the radiation heat loss to cold, interior outer walls would be less, and the ambient air
temperature reduction would be less. Thus, energy can be conserved if low emissivity
interior wall paints are utilized.
David
Page, of Tech Traders, Inc., asked Geoscience to investigate this thermal system.
MATHEMATICAL THERMAL ROOM MODEL THAT
DEFINES ENERGY SAVINGS VIA LOW IR EMISSIVITY PAINTS
This thermal room model describes heat
transfer processes that are operative in the wintertime. Specifically, convection from
warm room air and radiation from warm inside walls to the inside surface of the outer room
wall surface are conducted through the outer room wall and finally lost by convection and
radiation to the ambient, cold outside air and the cold outside surroundings. The
equations that define the heat transfer follow:
1)*

2)

3)

*
In this thermal model, it is postulated that the air and mean radiant temperatures are
equal, in the building room as well as in the outside environment, respectively.
Upon
rearranging Equations (1), (2) and (3) and taking note that the three heat fluxes in the
three equations are all equal at steady state, one adds the three equations and obtains,

The denominator in this Equation is the total
thermal resistance of this thermal heat flow circuit.
THE EXPERIMENTAL SYSTEM
A
wall test panel having an R-value of 2.75 hr ft2 °F/Btu was chosen to perform this test
work. It is pointed out that a typical building wall R value is about 11 hr ft2 °F/Btu
and the R value for a window system with a ½ air space between two
glass
panes is about 0.6 hr ft2 °F/Btu. Thus, it was thought to be appropriate to use a panel
having an intermediate R value for the subject test effort* (specifically, a R value of
2.75 hr ft2 °F/Btu). The surfaces of the panel were instrumented with surface
thermocouples and a thin, calibrated heat flux transducer was located on the cold side of
the wall panel. A cardboard box with an open side was placed over the hot side of the test
panel; this box then simulated a building room. A large plate electric heater was located
opposite the panel to heat the simulated building room. Hot and cold air thermocouples, as
well as a hot wall room thermocouple were also added to the system. The various heat
transfer processes that occur in the test system were previously defined in section II
above.
Test Procedure
The hot and cold panel surface temperatures,
the hot and cold air temperatures and the hot wall temperatures and steady state heat
fluxes were measured. One set of data was obtained for the case where the room walls and
the test panel interior surface were painted with ordinary house paint; another set of
data was obtained for the case where INSULADD paint was used.
From the two sets of data, the energy savings that accrue when using Insuladd is
determined.
*In
future testing, it would be better to perform two separate tests, one where only a wall is
used and another test where only a window is used.
Test Results
The
test results for the two paint types follow:
Test
System
Test System
ORDINARY
PAINT INSULADD PAINT
Heater
power, watts
42.5
37.9
Wall
panel heat flux, Btu/hr ft2
2.38 1.97
Hot
wall surface temperature, °F 100.2
99.0
Hot
side temperature of wall panel, °F
90.8
91.8
Hot
air temperature, °F
92.1
91.2
Cold
air temperature, °F
78.8
79.5
Total
thermal resistance
(air
to air) hr ft2 °F/Btu
5.59
5.94
CONCLUDING COMMENTS BY TECH TRADERS INC.
The
results outlined in the previous section clearly demonstrate energy Savings as a result of
using INSULADD®; specifically the total thermal resistance
of the model has increased with a corresponding drop in the Heat Flux. Real life Energy
Surveys find that the energy savings realized from the inclusion of INSULADD®
into interior house paint ranges from 10% to 22% depending on the type of construction,
location, and exposure of the home. An energy savings increase of only 10% in actual heat
flux (heat loss) can equate to a much greater increase in actual energy savings due to the
increased amount of time that Insuladd helps a homes interior remain in the human
comfort zone. The
human
comfort zone is that small range of temperature where humans (and animals) feel most
comfortable. This zone is quite narrow and tends to be between 70 degrees F. to 78 degrees
F. When indoor temperatures stray outside of the human comfort zone we use
heating or air-conditioning to bring the temperature back within the zone.